The dual door interface board enables OEM system integrators to connect TTL (D1/D0, Clock/Data), F/2F, 2-wire RS-485 devices, and door hardware. It includes:
Support for tri-state LED control and buzzer control
Six Form-C relay outputs for strike control or alarm signaling
Eight supervised or unsupervised inputs for door position, request to exit push button, and alarm contact monitoring
2-wire RS-485 communication with the system controller.
Dual Door Interface Components
Supplying Power to the Dual Door Interface
The dual door interface accepts 12 to 24 V DC for power on TB7 (VIN and GND).
Locate the power source as close to the MR52-S4 as possible.
Use a minimum of 18 AWG wire.
The VOUT terminal on TB7 provides the same voltage as VIN.
Important: Observe POLARITY on TB7.
Communication Wiring (SIO Communication Port)
The dual door interface communicates with a controller over a 2-wire RS-485 interface, supporting multi-drop communication on a bus of up to 4,000 feet (1,200 m).
Use a twisted-pair cable (minimum 24 AWG) with drain wire and shield. See dual door interface specifications.
Important: Install the RS-485 termination jumper (J4) only at each end of the communication line.
Reader Wiring
Each reader port supports a reader with TTL (D1/D0, Clock/Data) or 2-wire RS-485 signaling. Use the following cable types:
TTL (Wiegand): 6-conductor (18 AWG).
RS-485: 4-conductor twisted pair (24 AWG, 120Ω, shielded). Use one pair for data and one pair for power.
Power to the reader is 12 V DC, 600 mA maximum per reader port. Readers that require different voltage or have high current requirements must be powered separately with a common ground. Refer to the reader manufacturer specifications for cabling requirements. In the 2-wire LED mode the buzzer output drives the second LED. Reader port configuration is set via the host software.
Note:
For OSDP cable lengths greater than 200 feet (61 m) or EMF interference, install 120Ω +/- 2Ω resistor across RS-485 termination ends. This involves installing a resistor at the last reader in the OSDP bus, and setting the reader resistor jumper on the dual door interface (assuming it is at the EOL). See below for jumper details.
Data 0 and Data 1 wires for Wiegand may be reused for OSDP. However, standard Wiegand cable may not meet RS-485 twisted pair recommendations. The reuse of cable works best on shorter cable lengths at lower data rates.
JP8 and JP9 OSDP Termination Jumpers
The JP8 (reader port 1) and JP9 (reader port 2) jumpers control OSDP termination and are located just below the GND pins of each reader port (with the reader ports oriented at the top). Set the jumper to the ON position when using an OSDP reader. Set the jumper to the OFF position when using a non-OSDP reader.
Important: Failure to properly set the OSDP termination jumper could cause reader communication issues.
Reader Wiring Diagrams
Alarm Contact Wiring
There are eight inputs that are typically used to monitor door position, request to exit or alarm contacts. Input circuits can be configured as:
Unsupervised (2 states): Reporting as open or closed contact.
Supervised (6 states): Reporting as open or closed contact, open circuit, shorted circuit, grounded circuit*, or foreign voltage*.
(*Grounded and foreign voltage states are not a requirement of UL 294 and therefore not verified by UL.)
By default, inputs configured as supervised require two 1 kΩ, 1% resistors installed as close to the sensor as possible to ensure proper circuit supervision. Custom end-of-line (EOL) resistances can be configured via the host software.
Note: The input circuit wiring configurations shown are supported but may not be typical.
Inputs for Cabinet Tamper/Power Fault
Input TMP and input FLT are used for monitoring cabinet tamper and power failure with normally closed contacts. These two inputs are for contact closure monitoring only, and do not use EOL resistor(s).
Important: If these inputs are not used, install a short piece of wire at the input to indicate a safe condition.
Control Output Wiring
The dual door interface provides six Form-C relay contacts for controlling door strikes or other connected devices. When switching loads, especially inductive loads such as strikes, abnormal contact wear and premature contact failure can occur. Inductive loads can also generate electromagnetic interference (EMI), which may affect the operation of nearby equipment.
To improve reliability and extend relay life, always install a contact protection circuit. The circuit should be placed as close to the load as possible (within 12 inches [30 cm]). Installing it farther from the load reduces its effectiveness. Use wire gauges that are appropriately sized for the load current to prevent voltage loss.
Diode selection
Diode current rating > 1x strike current
Diode break down voltage: > 4x strike voltage
For 12 V DC or 24 V DC strike, diode 1N4002 (100V/1A) typical
Address and Baud Rate
DIP Switches 1 to 5 set the device address. Switches 6 and 7 set the communication baud rate. All other configuration settings are set via host software.
S8* | S7 | S6 | S5 | S4 | S3 | S2 | S1 | Selection |
|---|---|---|---|---|---|---|---|---|
off | off | off | off | off | Address 0 | |||
off | off | off | off | ON | Address 1 | |||
off | off | off | ON | off | Address 2 | |||
off | off | off | ON | ON | Address 3 | |||
off | off | ON | off | off | Address 4 | |||
off | off | ON | off | ON | Address 5 | |||
off | off | ON | ON | off | Address 6 | |||
off | off | ON | ON | ON | Address 7 | |||
off | ON | off | off | off | Address 8 | |||
off | ON | off | off | ON | Address 9 | |||
off | ON | off | ON | off | Address 10 | |||
off | ON | off | ON | ON | Address 11 | |||
off | ON | ON | off | off | Address 12 | |||
off | ON | ON | off | ON | Address 13 | |||
off | ON | ON | ON | off | Address 14 | |||
off | ON | ON | ON | ON | Address 15 | |||
ON | off | off | off | off | Address 16 | |||
ON | off | off | off | ON | Address 17 | |||
ON | off | off | ON | off | Address 18 | |||
ON | off | off | ON | ON | Address 19 | |||
ON | off | ON | off | off | Address 20 | |||
ON | off | ON | off | ON | Address 21 | |||
ON | off | ON | ON | off | Address 22 | |||
ON | off | ON | ON | ON | Address 23 | |||
ON | ON | off | off | off | Address 24 | |||
ON | ON | off | off | ON | Address 25 | |||
ON | ON | off | ON | off | Address 26 | |||
ON | ON | off | ON | ON | Address 27 | |||
ON | ON | ON | off | off | Address 28 | |||
ON | ON | ON | off | ON | Address 29 | |||
ON | ON | ON | ON | off | Address 30 | |||
ON | ON | ON | ON | ON | Address 31 | |||
off | off | 115,200 BPS | ||||||
ON | ON | 38,400 BPS |
* DIP switch 8 (S8) is reserved and not used.
Factory Reset
While not normally required, it is possible to perform a factory reset of the dual door interface, which deletes all onboard stored data. To perform the delete:
Set all DIP switches to OFF.
Remove power from the dual door interface.
Restore power to the dual door interface.
Within 3 seconds, toggle DIP switch 8 ON.
Note: LED behavior varies by SIO model.
Status LEDs
Power-up
All LEDs are OFF.
Initialization
Once power is applied, initialization of the module begins.
When initialization is completed, LEDs A through R2 are briefly sequenced ON then OFF.
Run Time
After the above sequence, the LEDs have the following meanings:
LED | Description |
|---|---|
A | Off-line: 1 sec rate, 20% ON |
On-line: Non-encrypted communication: 1 sec rate, 80% ON Encrypted communication: .1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .3 sec OFF | |
A | Error Indication: Waiting for application firmware to be downloaded: .1 sec ON, .1 sec OFF. |
B | SIO Communication Port Status: Indicates communication activity on the SIO communication port |
1 | Input Status: IN1 |
2 | Input Status: IN2 |
3 | Input Status: IN3 |
4 | Input Status: IN4 |
5 | Input Status: IN5 |
6 | Input Status: IN6 |
7 | Input Status: IN7 |
8 | Input Status: IN8 |
TMP | Cabinet tamper |
FLT | Power fault |
Input in the inactive state: OFF (briefly flashes ON every 3 seconds), Input in the active state: ON (briefly flashes OFF every 3 seconds), Input in a trouble state: Rapid Flash. | |
R1 | Reader port 1: |
R2 | Reader port 2: |
RLY1 through RLY6 | Illuminates when output relays RLY1 through RLY6 are energized. |
Specifications
Revision D assembly:
The Interface is for use in low voltage, class 2 circuits only.
The installation of this device must comply with all local fire and electrical codes.
Primary power: 12 to 24 V DC ± 10%, 550 mA maximum (reader current not included)
Outputs: Six Form-C relays:
Normally open contact (NO) contact: 5 A @ 30 V DC resistive
Normally closed contact (NC) contact: 3 A @ 30 V DC resistive
Inputs:
Eight unsupervised/supervised, standard EOL: 1k/1kΩ, 1%, ¼ watt
Two unsupervised, dedicated for cabinet tamper and UPS fault monitoring
Reader interface:
Power: 12 V DC, 600 mA maximum each reader port
Data inputs: TTL (Wiegand) compatible or 2-wire RS-485
LED output: TTL compatible, high > 3 V, low < 0.5 V, 5 mA source/sink maximum
Buzzer output: Open collector, 12 V DC open circuit maximum, 40 mA sink maximum
Communication: 2-wire RS-485: 38400, 115200 bps
Cable requirements (all ports shall use shielded conductors):
Power: One twisted pair, 18 AWG
RS-485 I/O devices: One twisted pair with drain wire and shield, 24 AWG, 120Ω impedance, 4,000 feet (1,200 m) maximum
Alarm inputs: One twisted pair per input, 30Ω maximum
Outputs: As required for the load
Reader data (TTL): 6-conductor, 18 AWG, 500 feet (150 m) maximum
Reader data (RS-485): One twisted pair with drain wire and shield, 24 AWG, 120Ω impedance, 2,000 feet (610 m) maximum
Mechanical:
Dimension: 6 inches (152 mm) W x 8 inches (203 mm) L x 1 inch (25.4 mm) H
Weight: 9.5 oz. (270 g) nominal
Environmental:
Temperature:
Storage: -55 to +85°C
Operating: 0 to +70°C
Humidity: 5 to 95% RHNC
Performance Levels
Evaluated to UL 294 8th edition and ULC 60839-11-1: Grade 2 and indoor dry.
Optional requirements of ULC 60839-11-1 items have not been evaluated.
Feature | Level |
|---|---|
ULC 60839-11-1 | Grade 2 |
Standby Power | I |
Endurance | IV |
Line Security | I |
Destructive Attack | I |
These specifications are subject to change without notice.
Liability
The Interface should only be used to control exits from areas where an alternative method for exit is available. Thisproduct is not intended for, nor is rated for operation in life-critical control applications. LenelS2 is not liable under any circumstances for loss or damage caused by or partially caused by the misapplication or malfunction of the product. LenelS2’s liability does not extend beyond the purchase price of the product.
Regulatory
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
The dual door interface board must be powered by an NRTL (Nationally Recognized Testing Laboratory) approved by Class 2 Listed Power Supply. Expansion port and supervised input functionality were not evaluated by UL.