The single door interface board enables system integrators to connect TTL (D1/D0, lock/Data) or RS-485 devices, and door hardware. It includes:
Support for tri-state LED control and buzzer control.
Two Form-C relay outputs for strike control or alarm signaling.
Two supervised or unsupervised inputs for door position and request-to-exit push-button monitoring.
2-wire RS-485 communication with the system controller.
Note: The single door interface requires 12 to 24 V DC for power.
Single Door Interface Components
Supplying Power to the Single Door Interface
The single door interface accepts 12 or 24 VDC for power on TB2 (VIN and GND).
Locate the power source as close to the MR50-S4 as possible.
Use a minimum of 18 AWG wire.
Important: Observe POLARITY on TB2.
Communication Wiring
The single door interface communicates with a controller over a half-duplex, multi-drop
2-wire RS-485 interface. The total cable length supports up to 4,000 feet (1,219 meters).
Use a twisted-pair cable (minimum 24 AWG) with drain wire and shield. See single door interface specifications.
Important: Install the RS-485 termination jumper (J601) only at each end of the communication line.
Reader Wiring
The reader port supports a reader with TTL (D1/D0, Clock/Data) or 2-wire RS-485 signaling. Use the following cable types:
TTL (Wiegand): 6-conductor (18 AWG)
RS-485: 4-conductor twisted pair (24 AWG, 120Ω, shielded). Use one pair for data and one pair for power
Power to the readers is 12 V DC, 600 mA maximum per reader port. Readers that require different voltage or have high current requirements must be powered separately with a common ground. Refer to the reader manufacturer specifications for cabling requirements. In the 2-wire LED mode the buzzer output is used to drive the second LED. Reader port configuration is set via the host software.
Note:
For OSDP cable lengths greater than 200 ft (61 m) or EMF interferences, install a 120Ω +/- 2Ω resistor across RS-485 termination ends. This involves installing a resistor at the last reader in the OSDP bus, and setting the reader resistor jumper on the MR50 (assuming it is a the EOL). See below for jumper details.
Data 0 and Data 1 wires for Wiegand may be reused for OSDP. However, standard Wiegand cable may not meet RS-485 twisted pair recommendations. The reuse of cable works best on shorter cable lengths at lower data rates.
J602 Reader Port Termination
The J602 jumper is located next to the reader port and controls OSDP termination. This jumper should be set to the ON position when using an OSDP reader. Set the jumper to the OFF position when using a non-OSDP reader.
Important: Failure to properly set the OSDP termination jumper could cause reader communication issues.
Reader Wiring Diagrams
Alarm Contact and Cabinet Tamper Input Wiring
The single door interface requires filtered 12 to 24 V DC ± 10% for power. Two inputs are typically used for door contact and exit push button monitoring. End of line resistors are required for input supervision, shown below.
Caution: The reader power output terminal, TB4 (12V), provides a fixed 12 VDC output regardless of the input voltage applied to the MR50-S4. Readers requiring a different operating voltage must be powered separately. TB4 (12V) is not current limited.
Control Output Wiring
The single door interface provides two Form-C relay contacts for controlling door strikes or other connected devices. When switching loads, especially inductive loads such as strikes, abnormal contact wear and premature contact failure can occur. Inductive loads can also generate electromagnetic interference (EMI), which may affect the operation of nearby equipment.
To improve reliability and extend relay life, always install a contact protection circuit. The circuit should be placed as close to the load as possible (within 12 inches [30 cm]). Installing it farther from the load reduces its effectiveness. Use wire gauges that are appropriately sized for the load current to prevent voltage loss.
Diode selection
Diode current rating: > 1x strike current
Diode breakdown voltage: > 4x strike voltage
For 12 V DC or 24 V DC strike, diode
1N4002 (100V/1A) typical.
Address and Baud Rate
Switches 1 to 5 select the device address. Switches 6 and 7 select the communication baud rate. All other configuration settings are set via host software.
S8* | S7 | S6 | S5 | S4 | S3 | S2 | S1 | Selection |
|---|---|---|---|---|---|---|---|---|
off | off | off | off | off | Address 0 | |||
off | off | off | off | ON | Address 1 | |||
off | off | off | ON | off | Address 2 | |||
off | off | off | ON | ON | Address 3 | |||
off | off | ON | off | off | Address 4 | |||
off | off | ON | off | ON | Address 5 | |||
off | off | ON | ON | off | Address 6 | |||
off | off | ON | ON | ON | Address 7 | |||
off | ON | off | off | off | Address 8 | |||
off | ON | off | off | ON | Address 9 | |||
off | ON | off | ON | off | Address 10 | |||
off | ON | off | ON | ON | Address 11 | |||
off | ON | ON | off | off | Address 12 | |||
off | ON | ON | off | ON | Address 13 | |||
off | ON | ON | ON | off | Address 14 | |||
off | ON | ON | ON | ON | Address 15 | |||
ON | off | off | off | off | Address 16 | |||
ON | off | off | off | ON | Address 17 | |||
ON | off | off | ON | off | Address 18 | |||
ON | off | off | ON | ON | Address 19 | |||
ON | off | ON | off | off | Address 20 | |||
ON | off | ON | off | ON | Address 21 | |||
ON | off | ON | ON | off | Address 22 | |||
ON | off | ON | ON | ON | Address 23 | |||
ON | ON | off | off | off | Address 24 | |||
ON | ON | off | off | ON | Address 25 | |||
ON | ON | off | ON | off | Address 26 | |||
ON | ON | off | ON | ON | Address 27 | |||
ON | ON | ON | off | off | Address 28 | |||
ON | ON | ON | off | ON | Address 29 | |||
ON | ON | ON | ON | off | Address 30 | |||
ON | ON | ON | ON | ON | Address 31 | |||
off | off | 115,200 BPS | ||||||
ON | ON | 38,400 BPS |
* DIP switch 8 (S8) is reserved and not used.
Factory Reset
While not normally required, it is possible to perform a factory reset of the single door interface, which deletes all onboard stored data. To perform the delete:
Set all DIP switches to OFF.
Remove power from the single door interface.
Restore power to the single door interface.
Within 3 seconds, toggle DIP switch 8 ON.
Note: LED behavior varies by SIO model.
Status LEDs
Power-up
All LEDs are OFF.
Initialization
Once power is applied, initialization of the module begins. The A LED is turned ON at the beginning of initialization.
Run Time
After a successful initialization, the LEDs have the following meanings:
LED | Description |
|---|---|
A | Off-line: 1 second rate, 20% ON, 80% OFF |
On-line: Non-encrypted communication: 1 second rate, 80% ON, 20% OFF Encrypted communication: .1 S ON, .1 S OFF, .1 S ON, .1 S OFF, .1 S ON, .1 S OFF, .1 sec ON, .3 S OFF | |
A | Error Indication: Waiting for application firmware to be downloaded: .1 S ON, .1 S OFF |
B | SIO communication port status: Indicates communication activity on the SIO communication port. |
RLY1 and RLY2 | Illuminates when output relays RLY1 or RLY2 are energized. |
Specifications
Revision E assembly: The Interface is for use in low voltage, class 2 circuits only.
Primary power: 12 to 24 V DC ± 10%, 150 mA maximum (reader current not included)
Outputs: Two Form-C relays:
Normally open contact (NO) contact: 5 A @ 30 V DC resistive
Normally closed contact (NC) contact: 3 A @ 30 V DC resistive
Inputs:
Two unsupervised/supervised, standard EOL, 1k/1kΩ, 1%, ¼ watt
One unsupervised, dedicated for cabinet tamper
Reader interface:
Reader power: 12 V DC, 600 mA maximum
Reader LED output: TTL (Wiegand) compatible, high > 3 V, low < 0.5 V, 5 mA source/sink maximum
Buzzer output: Open collector, 12 V DC open circuit maximum, 40 mA sink maximum
Data inputs: TTL compatible or 2-wire RS-485
Communication: 2-wire RS-485: 38400, 115200 bps
Cable requirements (all ports shall use shielded conductors):
Power: One twisted pair, 18 AWG
RS-485 I/O devices: One twisted pair with drain wire and shield, 24 AWG, 120Ω impedance, 4,000 feet (1,200 m) maximum
Alarm inputs: One twisted pair per input, 30Ω maximum
Outputs: As required for the load
Reader data (TTL): 6-conductor, 18 AWG, 500 feet (150 m) maximum
Reader data (RS-485): One twisted pair with drain wire and shield, 24 AWG, 120Ω impedance, 2,000 feet (610 m) maximum
Mechanical:
Dimension: 4.25 inches (108 mm) W x 2.75 inches (70 mm) L x 1 inch (25.4 mm) H
Weight: 2.9 oz. (83 g) nominal
Environmental:
Temperature:
Storage: -55 to +85°C
Operating: -40 to +75°C (UL Verified for 0 to 70°C)
Humidity: 5 to 95% RHNC
Performance Levels
Evaluated to UL 294 8th edition and ULC 60839-11-1: Grade 2 and indoor dry.
Optional requirements of ULC 60839-11-1 items have not been evaluated.
Feature | Level |
|---|---|
ULC 60839-11-1 | Grade 2 |
Standby Power | I |
Endurance | IV |
Line Security | I |
Destructive Attack | I |
These specifications are subject to change without notice.
Liability
The Interface should only be used to control exits from areas where an alternative method for exit is available. Thisproduct is not intended for, nor is rated for operation in life-critical control applications. LenelS2 is not liable under any circumstances for loss or damage caused by or partially caused by the misapplication or malfunction of the product. LenelS2’s liability does not extend beyond the purchase price of the product.
Regulatory
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
The single door interface board must be powered by an NRTL (Nationally Recognized Testing Laboratory) approved by Class 2 Listed Power Supply. Expansion port and supervised input functionality were not evaluated by UL.